SCDLM-MA
Multi-compartment smoke control dampers with manual and automatic activation

Characteristics:
• Rectangular fire damper from 200 x 430 mm to 1200 x 2030 mm.
• CE-certified according to EN 12101-8.
• 250 mm wide damper.
• Tested according to EN 1366-10.
• Classified according to EN 13501-4+A1 as EIS 120, with AA/MA positioning for Multi-compartment fire protection.
• Cycle test class Cmod according to EN 12101-8.
• External housing leakage Class C, internal leakage Class 3 according to EN 1751.
• Damper actuation via 24 V or 230 V electric actuator.
• Designed for systems with automatic or manual activation.
• Recommended maximum speed 12 m/s, allowable pressure up to 500 Pa, or vacuum up to -1000 Pa.
• The damper can be supplied with or without flanges.
• The dampers are only suitable for vertical installation with the blade axis in a horizontal position.
• Working temperature: -30 ºC +50 ºC.
Downloads:
Technical datasheet

Price finder
Search for a product through its name or code and we will show you its price (VAT not included).